Application and analysis of valves in engineering design

Application and analysis of valves in engineering design
0
By analyzing the design conditions and the characteristics of the valve operating principle, static hydraulic balancing valves, self-operated flow control valves, etc. were analyzed. This study from the perspective of reducing the amount of system investment and energy consumption, the need to make the use of two types of valves, and the actual design of the two types of balancing valves debugging and other explanations.
1 Discussion on the application of static hydraulic balancing valve
1.1 Design conditions of hydraulic disorders
An excellent HVAC system can fully ensure that the equipment under full load conditions, all users can obtain the design is the amount of water required, but also to fully ensure the safety and economic efficiency of the system operation, effectively reduce customer complaints about water and water waste and other situations, only such a system can be considered a hydronic balance of the system. If the system does not have these features then it can be called an unbalanced system. In general, if part of the hydraulic system, the user's use of pressure head is greater than the designed pressure head, then the user's actual water flow will exceed the designed flow, which will affect the actual flow of the other loops, we call the hydraulic dislocation in this case for the static hydraulic dislocation, static hydraulic dislocation is usually due to the design of the system or the construction of the reasons, the static hydraulic Disorder is the system itself can not be avoided.
There is also a state in which the actual flow rate of all user terminals in the system is greater than or equal to the value of the system design. In this case the flow rate can fully satisfy the customer's demand, so this state generally does not cause customer complaints, so this situation will not cause the designer's concern. In general, we use the formula ΔP = SG2 to describe the relationship that exists between the various physical factors of the hydraulic condition in the state of the pipe network of the closed loop (Δp is the differential pressure, S is the pipe network impedance, G is the flow rate).
In the country has not been introduced between the concept of static hydraulic balancing valve, usually the use of globe valves or butterfly valves to control the static hydraulic system. Because these valves have the advantages of simple structure, easy to operate, affordable and so on in the country has been widely used.
Designers in a clear design on the basis of selection, in the system for full-load conditions should be the end of all the temperature-controlled electric valve open, and will be one to three of the end of the flow designed for 33m3 / h. Its valves are kept 100% open, then the actual flow of the end of the first 39m3 / h; two 35m3 / h; three 31m3 / h, when the pump working point parameters head About 19m, the flow rate of about 105m3 / h, so that the system has a hydraulic imbalance phenomenon.
Can be adjusted by adjusting the opening of the first and second section valve to adjust the system, the specific operation is: the first heating control valve differential pressure to reduce 40kPa; second differential pressure to reduce 20kPa, to ensure that the three end nodes coil heating control valve resistance at both ends are maintained at 80kPa, and at the same time to meet the design of the flow of 33m3 / h, the pump head in 20m, the flow rate of 100m3 / h, so that the static balance of the system. Therefore, we do not need to regulate all the section valve can realize the static hydraulic balance of the system, so we are in the static hydraulic balance of the end of the branch configuration of the section valve, do not need to configure one by one, that is to say, the static hydraulic balance valve is not the only way to deal with this kind of problem.
In the current situation, the vast majority of HVAC hydronic system design is only for the end of the branch for the design of the flow rate of the label, basically will not pay attention to the end of the differential pressure value of the relevant standards and requirements, in the specific operation process, some need to manually complete the balance of the adjustment basically rely on the design, construction, and operation and maintenance personnel to complete the experience of the system belongs to a kind of theoretical support for the system adjustment method. It belongs to a system adjustment method without theoretical support. But from the actual effect, this kind of regulation method without theoretical support does bring some effect for the system of hydraulic disorders.
1.2 Static hydraulic balance valve and hydraulic balance
Static hydraulic balance valve is essentially a multi-functional manual control valve, static balance valve has a single valve multi-functional characteristics, “based on experimental data to be able to characterize, when Δp is a constant state, then the static hydraulic balance valve does not have obvious advantages of regulating, so in the current technological conditions, the use of static hydraulic balance valves directly instead of the traditional hydraulic control valve is not mature enough.
In the current static hydraulic balancing valve market circulation of balancing valve products with flow measurement, valve opening screen, pre-flow, emptying and other functions. The use of static hydraulic balancing valves can be measured in a timely manner through a specific instrument on the flow, but also can play the role of the switch. Once the balancing valve is completed after commissioning, we can not open the valve to change by will. This is mainly in view of the later maintenance problems, we have the valve body spindle sealing treatment. Work such as measurements do not need to run in the case of interruption of the system, can be done on site, and does not need to destroy the overall insulation of the system can be realized. However, from the point of view of its cost-effectiveness, its price relative to the same flow rate of centrifugal pumps do not have an advantage, while in the current domestic market static hydraulic balancing valve there are still some problems. For incompressible fluids, static hydraulic balancing valve can be used as a local resistance adjustment of the throttle component.
Static hydraulic balancing valve can rely on its valve opening to regulate the flow resistance of the valve, the valve openings correspond to a KV value, and different openings of the KV value is fixed, so we just need to get the Δp on the scene to derive its Q value. In order to facilitate the measurement, we generally set up a special pressure test hole for the two ports of the static hydraulic balancing valve, this component is usually used as a throttle. When we carry out engineering commissioning work, we use the relevant hydraulic balancing commissioning equipment provided by the manufacturer to measure the Δp value, and then use the relevant software to find out the corresponding KV value, so as to calculate the specific Q value. At this time, Δp as a specific measurement value; KV as a set value, when it meets the ΔP = 0.1MPa conditions; Q is the specific calculation value, the factors affecting the speed of its calculation mainly include the actual overflow area of the valve as well as the roughness of the estimated value of the accuracy.
Attention needs to be paid to the fact that we use the balance valve to deal with the relevant hydraulic imbalance problem is the need for certain support conditions “based on the operation mechanism of the static hydraulic balance valve we can know that the static hydraulic balance valve, but after locking, Δp fluctuations in the value of the water flowing through the valve will cause damage to the constancy of the water, resulting in the calibration of the flow rate value changes.
In the current market, many suppliers of static hydraulic balancing valves have explained that their products have a flow preset function, but in practice, it is difficult to choose a suitable KVS value, because the current market balancing valves do not give a continuous KVS value, and not in accordance with the actual need to give the adjustment value of KVS, therefore, when we set the flow according to the supplier to provide the KVS value Therefore, when we set the flow rate according to the KVS value provided by the supplier, there will be a certain deviation, which does not meet the needs of actual regulation. Due to the inability to clarify the field Δp value and the valve opening adjustment caused by the change in the KV value, in the specific process of practice found that if you can not clarify the fouling coefficient of the inner wall of the valve or when the value of its RE does not exceed 3,500, the flow rate of Q value may appear a large deviation in the calculation. Therefore, in the static hydraulic balance judgment, it is necessary to ensure that all the self-operated valves have reached the corresponding design parameter values, to ensure that all the end equipment temperature control valves in the fully open state, and can ensure that its flow rate to meet the design of the required amount.
Regardless of whether the balance valve has a flow preset function, after completing the installation of the water system, it is necessary to regulate all the valves to ensure that the static water balancing valve flow Q value can reach the design requirements, so as to ensure that the pipe network can be realized in the state of the working conditions of the water balance. At this time, the static water balancing valve is locked on the opening degree, and in the operation process can not be set on the opening degree of the smooth adjustment. At the same time, we should also do a good job of recording the relevant data stored in the system equipment commissioning files, to facilitate the development of future maintenance work.
In addition, due to different equipment suppliers to provide the computer software KV value is not uniform, resulting in different suppliers to provide products supporting the commissioning instrumentation can not be realized interoperability. In static hydraulic balancing valves, all static hydraulic balancing valves are set up with a cavity behind their hair plugs, and this cavity becomes the main retention point for dirt during online operation.
2 Self-operated flow control valve
2.1 Self-operated flow control valve principle of operation
Self-operated flow control valve is a new type of control valve on the market, self-operated flow control valve compared to the traditional manual flow control valve is superior to its ability to achieve automatic flow adjustment, without the need for external power can be completed. In the actual use of the process found in the closed water circulation system using this self-operated flow control valves can facilitate the realization of the system's flow distribution, dynamic balance, so as to simplify the system commissioning purposes. Based on these advantages, self-operated control valves in the heating and air conditioning project has been favored by many manufacturers. Self-operated flow control valve belongs to a two-valve combination structure, consisting of a manual control valve and automatic balancing valve, they are responsible for setting the flow rate and maintaining a constant flow rate.
In the manual control valve, KVS is the flow coefficient of the manual control valve port, and P2-P3 is the pressure difference coefficient between the two sides of the manual control valve port. the size of the KVS is closely related to the degree of openness, openness is unchanged, the KVS is a variable, if the P2-P3 is unchanged, the C does not change. the P2-P3 is kept unchanged depends mainly on the balancing valve. For example, the import and export pressure difference Pl-P3 becomes larger, the use of dynamic pressure film and spring force prompted the balance switch automatically adjusts the small, P1-P2 will become larger, to maintain P2-P3 unchanged, so the formation of a fixed; on the contrary, P1-P3 becomes smaller, the balance switch automatically adjusts the large, P1-P2 will become smaller, to maintain P2-P3 unchanged, so as to complete the fixation of the “manual switch regulating group of the angle at which each valve open Size of each valve of the manual switch regulator group has a corresponding flow rate, the relationship between the angle of each valve open and the flow rate by the test bench to show the experimental standard decision, but also has the corresponding openness of the display and locking equipment.
2.2 Self-operated flow control valve in the water mixing system applications
Self-operated flow control valves do not need to rely on external power but rely on their own media pressure difference to achieve control, self-operated flow control valves are equipped with automatic flow control components, the components can realize the flow equilibrium, through this function from the fundamental solution to the problem of hydraulic imbalance. Self-operated flow control valves are very simple to install and easy to adjust, the use of the process of consuming less energy, which increases the heating area can reach between 25% -30%, greatly improving the stability of its operation, to ensure the quality of heating. When we carry out the transformation of the water mixing system, first of all, the hydraulic calculation, the heating area, the ring flow to and the corresponding heating pipe diameter and other factors to analyze, according to these data information to select the appropriate flow control valve, according to the temperature to regulate the size of the flow, and then with the help of self-operated flow control valves with a unique function to achieve stability of the mixing of the water pressure, flow, and temperature, which fully ensures that the water mixing station This can fully ensure that the mixing station can obtain a relatively stable flow between the system to ensure the balance of the operation.

We are committed to excellence in everything we do and look forward to working with you!

QUESTIONS OR CONSULTING

Contact Information

Fill up the form and we’ll get back to you in few hours.

+86 22 60612677

daniellee@runningda.com

No.88 Zhuhai Road, Tanggu Marine High-tech Zone, Binhai New Area, Tianjin 300459, China.

Call Us

+86 18526585151

电话
WhatsApp
Skype
微信